All Ethernet Network faults will activate the alarm relay. Use the fault messages on the Alarm screen along with this table to diagnose and correct Ethernet network problems. You can also use the Network Status and Node Configuration screens, and the Ethernet Controller Troubleshooting to diagnose problems with the remote nodes.
Error Code |
Message/Condition |
Correction |
901 |
I/O error |
Check Ethernet wiring. Remote node could be disconnected from network or turned off |
902 |
Port or socket open error |
Programming error. Contact Nordson technical support |
903 |
Serial port already open |
Programming error. Contact Nordson technical support |
904 |
TCP/IP connection error |
Check Ethernet wiring. Remote node could be disconnected from network or turned off |
905 |
TCP/IP Connection closed by remote peer fault (any remote node fault) |
Ethernet network communication with the remote node has been lost. This fault may be a normal response to removing electrical power from the remote node. If the remote node is an in/out positioner or reciprocator and communication is lost while operating in Auto mode, the machine will move to the Park position. Check the Network Node Status screen. If communication is lost the node icon should turn red. If no nodes are red, check the Network Node Configuration screen to find the device associated with the faulted node IP address. If multiple node faults are displayed:
If a single node fault is displayed:
|
906 |
Socket library error |
Programming error. Contact Nordson technical support |
907 |
TCP port already bound |
Programming error. Contact Nordson technical support |
908 |
Listen failed |
Programming error. Contact Nordson technical support |
909 |
File descriptors exceeded |
Programming error. Contact Nordson technical support |
910 |
No permission to access serial or TCP port |
Programming error. Contact Nordson technical support |
911 |
TCP port not available |
Programming error. Contact Nordson technical support |
917 |
Checksum error |
Noise in network. Check for loose connections or Ethernet cables routed parallel to high voltage or VFDs |
918 |
Invalid frame error |
Noise in network. Check for loose connections or Ethernet cables routed parallel to high voltage or VFDs |
919 |
Invalid reply error |
Noise in network. Check for loose connections or Ethernet cables routed parallel to high voltage or VFDs |
920 |
Reply time-out |
Noise in network. Check for loose connections or Ethernet cables routed parallel to high voltage or VFDs |
921 |
Modbus exception response |
Programming error or remote hardware error. Check Fieldbus controller functions. Refer to Ethernet Controller Troubleshooting |
925 |
Illegal Function exception response |
Programming error or remote hardware error. Check Fieldbus controller functions. Refer to Ethernet Controller Troubleshooting |
926 |
Illegal Data Address exception response |
Programming error or remote hardware error. Check Fieldbus controller functions. Refer to Ethernet Controller Troubleshooting |
927 |
Illegal Data Value exception response |
Programming error or remote hardware error. Check Fieldbus controller functions. Refer to Ethernet Controller Troubleshooting |
928 |
Slave Device Failure exception response |
Programming error or remote hardware error. Check Fieldbus controller functions. Refer to Ethernet Controller Troubleshooting |
3100, 3200 |
Watchdog Fault |
Control program in remote node controller is not running, or controller has no program installed NOTE: This fault may be a normal response to removing electrical power from the remote node
|
- |
Operation was successful |
Normal operation. No action required |
- |
Illegal argument error |
Programming error. Contact Nordson technical support |
- |
Illegal state error |
Programming error. Contact Nordson technical support |
- |
Evaluation expired |
Programming error. Contact Nordson technical support |
- |
I/O error class |
Programming error. Contact Nordson technical support |
|
Fieldbus protocol error class |
Programming error. Contact Nordson technical support |