FailSafe Mode

NOTE: Only Nordson service personnel can access this setting. Contact your Nordson representative if you need to change this setting.

The FailSafe mode allows you to set the normal operating state of the fault relays. Setting the relays to Off indicates that the relay coils are deenergized during operation and will energize when a fault occurs. Setting the relays to On indicates that the relay coils are energized during operation and will deenergize when a fault occurs.

Default Setting: On

  1. Icon_TOOLSGREEN.JPG Touch the information and setup bar on the appropriate Spray Monitor faceplate.

  2. Icon_SM.jpg Select Spray Monitor Configuration from the drop-down menu.

  3. Icon_SERVICE.JPG Touch the Service button at the top of the Spray Monitor Configuration window.

  1. Use the scroll bar at the right-hand side of the window to scroll down to the lower half of the window.

  2. Touch the FailSafe button to change the setting to Off or On.

OFF - Relays are normally deenergized. Relay coil energizes when a fault occurs.

ON - Relays are normally energized. Relay coil deenergizes when a fault occurs. This is the default setting.