The Extended Can-In-Pocket (CIP) output feature adds vacuum detect, gun mount position, and belt spin detect to the standard CIP detection function. Each additional function requires a proximity switch or other sensor connected to the PRx Module.
The PRx module combines the signals from these sensors and sends a single CIP signal to the Spray Monitor. If one of the sensor signals is not correct, then the Spray Monitor does not receive the CIP signal and generates a CIP fault. The iTrax system identifies the sensor causing the fault.
NOTE: Only Nordson service personnel can access this setting. Contact your Nordson representative if you need to change this setting.
Use this procedure to set up the XCIP functions.
Touch the information and setup
bar on the appropriate PRx Module faceplate.
Select
PRx Configuration from the
drop-down menu.
Select
the Service button at the
top of the PRx Configuration window.
Enable XCIP
Output and set the desired
output polarity. The buttons toggle On
and Off and Low
and High.
Enable the desired functions and set their polarity:
Vacuum Detect, Gun Mount Pos, CIP Prox SW, Belt
Spin Detect.