Warning: Electrical/Mechanical Noise |
|
Electrical or mechanical noise in the spray system is affecting the iTrax Spray Monitor. |
|
Possible Cause |
Resolution |
Pressure transducer malfunction |
Check the pressure transducer wiring. Make sure the twisted pair wiring is connected properly. Check for correct voltage on the excitation circuit. Replace the pressure transducer if necessary. |
Electrical connections shorted, loose, or incorrect; interference from other power sources or wires |
Check all iTrax system electrical connections. Check and relocate possible sources of interference. |
Fluid supply system |
Make sure vibrations in the fluid supply system are dampened. Minimize pressure fluctuations. |